The Robertshaw® Universal Ignition Control Uni-Kit® is available in both nonlockout (780-001) and lockout (780-002). The 780-003 is lockout with a prepurge function. The kit a flame sense circuit that automatically detects the presence of a remote sense probe (2 rod system) or it switches to local sense (1 rod system) utilizing the pilot assembly as a sensing source. If both systems are provided, failure of one causes automatic reversion to the other.
- In the event of flame failure, the main gas supply is automatically shut off.
- Provides 3 tries for ignition, each period lasts 60 seconds.
- 5-minute time delay between ignition attempts.
- Easy-to-install with complete in-depth installation instructions
- Pilot and main valves draw 1 Amp at 0.5 power factor
- Combined load at 1.5 Amps at 0.4 power factor
- 95% relative humidity noncondensing at 104 °F
Specifications:
- Series Application: 780-002, 24V Intermittent Pilot Ignition Uni-Kit
- Spark Rate: 3 to 4 per second
- Maximum Total Current Load: 1.5 A
- Flame Failure Re-Ignition Time: 0.8 seconds
- Thermostat Anticipator Setting: 0.7 A
- Temperature Range: -40 °F to 175 °F
- Flame Sensor Current: 0.7 mA DC @ 25 °C
- Transformer: 24 V AC, 20 VA
- Control Voltage: 24 V AC, 50/60 Hz