Safety relay (standalone), inputs: 1/2-channel wiring with/without detection of shorts across contacts, outputs: 2 N/O,automatic/manual start, UB 24 V AC/DC, width: 22.5 mm, screw terminals integrated, monitoring of E-STOP, safety gates.
General data
- Approval
- CCC
- CE
- UKCA
- cULus Listed
- KOSHA
- EAC (Eurasian)
- TÜV
Electrical data
- Supply voltage (V) 24 V
- Type of supply voltage U1 AC/DC
- Power consumption AC 4.5 VA
- Power consumption DC 2 W
- Inputs
- Semiconductor outputs
- Number of semicond. outputs 0
Relay outputs
- Utilisation cat. AC/DC1 stand. EN 60947-4-1
- Voltage AC1 safety cont. 240 V
- Max. current AC1 safety cont. 6 A
- Voltage DC1 safety cont. 24 V
- Max. current DC1 safety cont. 6 A
- Utilisation cat. AC15/DC13sta. EN 60947-5-1
- Voltage AC15 safety cont. 230 V
- Max. current AC15 safety cont. 5 A
- Voltage DC13 safety cont. 24 V
- Safety contacts: AC at UL 240 VAC G. P.
- Safety contacts: pilot duty C300, R300
- Relay contact material AgSnO2
- Addit. contact details relay + 0.2 µm Au
Environmental data
- Climatic suitability to ... EN 60068-2-78
- Ambient temperature -10 - 55 °C
- Humidity rating 93 % r. h. at 40 °C
- Condensation permitted? Not permitted
- EMC to standard ...
- EN 60947-5-1
- EN 61000-6-2
- EN 61326-3-1
- Vibration to standard ... EN 60068-2-6
- Clearance & creepage dist. to EN 60947-1
- Overvoltage category III / II
- Pollution degree clear.&creep. 2
- Protection type, mounting
- Protection type, housing IP40
- Terminal protection type
Mechanical data
- Mounting position any
- Housing material lower section
- Housing material front plate ABS UL 94 V0
- Housing material upper part
- Connection terminal Screw terminal
- Terminal style fixed
- Flex. cond. c/s AWG info 24 - 10 AWG
- Height dimension 87 mm
- Width dimension 22.5 mm
- Depth dimension 121 mm
- Net weight 195 g
- Gross weight 205 g