PNOZsigma voltage monitoring relay up to PL e and SIL Cl 3, UB = 100 - 240 V AC/DC, outputs: 3 N/O, 1 N/C, 6 auxiliaryoutputs, width: 90 mm, plug-in spring-loaded terminals, expansion with PNOZsigma contact expansions.
General data
- Approval
- CE
- CCC
- UKCA
- cULus Listed
- EAC (Eurasian)
- TÜV
Electrical data
- Purpose of U1 Device supply
- Supply voltage (V) 100 - 240 V
- Type of supply voltage U1 AC/DC
- Power consumption AC 10.5
- Power consumption DC 8
- Measuring circuit
- Meas. circ. frequ. range (Hz) 50 ; 60
- Inputs
- Semiconductor outputs
- Number of semicond. outputs 6
- Tolerance ext. volt. DC S/C P_HALBL_TOLERANZ_UB_EXT_DC_-20 %/+20 %
- Semiconductor outputs (standard)
- Galv. isol. n/safe SC O P_HI_HLA_TRENNUNG_GALVAN_ja
- Short circ. prot. n/safe S/C O P_HI_HLA_KURZSCHLUSSFEST_ja
- Signal level at 1 n/safe S/C O P_HI_HLA_SIGNALPEGEL_HIGH_UB - 2,5 V DC bei 0,05 A
Relay outputs
- Utilisation cat. AC/DC1 stand. P_SCHALTVERMOEGEN_NACH_EN 60947-4-1
- Voltage AC1 safety cont. 250
- Max. current AC1 safety cont. 6
- Voltage DC1 safety cont. 24
- Max. current DC1 safety cont. 6
- Utilisation cat. AC15/DC13sta. P_SCHALTVERMOEGEN_13_NACH_EN 60947-5-1
- Voltage AC15 safety cont. 230
- Max. current AC15 safety cont. 3
- Voltage DC13 safety cont. 24
- Safety contacts: AC at UL P_SCHALT_SI_AC_UL_U_B_250 V AC G.U. (same polarity)
- Safety contacts: pilot duty P_SCHALT_SI_UL_PD_R300, B300 for NO contact only
- Relay contact material P_KONT_MAT_AgCuNi
- Addit. contact details relay P_KONT_MAT_ZUSATZ_+ 0,2 µm Au
Environmental data
- Climatic suitability to ... P_KLIMA_EN 60068-2-2
- P_KLIMA_EN 60068-2-1
- P_KLIMA_EN 60068-2-78
- P_KLIMA_EN 60068-2-14
- Ambient temperature -10 - 55 °C
- Humidity rating P_FEUCHTE_WERT_93 % r. F. bei 40 °C
- Condensation permitted? Not permitted
- EMC to standard ... EN 60255-26
- EN 61326-3-1
- Vibration to standard ... EN 60255-21-1
- Test severity class vibration P_PRUEFSCHAERFEKLASSE_SCHWING_Klasse 1
- Test severity class shock P_PRUEFSCHAERFEKLASSE_SCHOCK_Klasse 1
- Earthquake to standard 1 P_ERDBEBEN_NORM_1_EN 60255-21-3
- Test severity class earthquake P_PRUEFSCHAERFEKLASSE_ERDBEBEN_Klasse 0
- Test severity class cont.shock P_PRUEFSCHAERFEKLASSE_D_SCHOCK_Klasse 1
- Clearance & creepage dist. to EN 60255-27
- Overvoltage category III
- Pollution degree clear.&creep. 2
- Protection type, mounting
- Protection type, housing IP20
- Terminal protection type
Mechanical data
- Mounting position any
- Housing material lower section P_GEHAEUSE_MAT_U_PC
- Housing material front plate P_GEHAEUSE_MAT_F_PC
- Housing material upper part PC
- Connection terminal Spring-loaded terminal
- Terminal style plug-in
- Height dimension 98 mm
- Width dimension 90 mm
- Depth dimension 120 mm
- Net weight 655 g
- Gross weight 665 g