RFiD safety switch 2 safe SC outputs, 8-pin M12 male connector, with 1.5 m cable, one actuation direction, support for SDD, IP67 switching distance depends on the actuator, series connection, PU = 1piece coded switch with actuator.
Specifications:
- Approval: CE, UKCA, cULus Listed, FCC, IC, EAC (Eurasian), TÜV
- Sensor principle: Transponder
- Coding level to ISO 14119: Low
- Classification to EN 60947-5-3: PDDB
- Transponder coding: Coded
- Suitable for series connection: Yes
- Unit type: Sensor
- Supply voltage: 24 V
- Type of supply voltage (U1): DC
- Power consumption (DC): 1 W
- Number of inputs: 2
- DC voltage at input: 24 V DC
- Number of OSSD outputs: 2
- Number of signaling outputs: 1
- Potential isolation S/C O: No
- S/C output short circuit proof: Yes
- Utilisation category (EN 60947-1): DC-12
- Ambient temperature standard: EN 60068-2-14
- Ambient temperature: -25 to 70 °C
- Max. ambient temp. at Hmax: +60 °C
- Max. ambient temp. at 2000 m: +70 °C
- Storage temperature standard: EN 60068-2-1/-2
- Climatic suitability standard: EN 60068-2-78
- Humidity rating: 93% r.h. at 40 °C
- Permissible operating height (ASL): 4000 m
- EMC standard: EN 60947-5-3
- Vibration standard: EN 60947-5-2
- Shock resistance: 30g
- Overvoltage category: III
- Pollution degree (clear. & creep.): 3
- Protection type (housing): IP6K9K
- Change op. distance temp. act.1: ±0.01 mm/°C
- Change op. distance temp. act.2: ±0.1 mm/°C
- Change op. distance temp. act.3: ±0.01 mm/°C
- Change op. distance temp. act.4: ±0.01 mm/°C
- Bend radius (when laying) K1: 5 × Ø
- Sensor flush-mounted: Yes (follow installation guide)
- Connection type: M12, 8-pin male
- Cable type: Li9Y11Y, 8 × 0.14 mm²
- Housing material (upper part): PBT
- Height: 37 mm
- Width: 26 mm
- Depth: 18 mm
- Gross weight: 123 g
- Operating frequency: 122–128 kHz