Catalog Description:MS132-10 Manual Motor Starter 6.3 ... 10 A
Long Description:The MS132-10 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 10.0 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 100 kA at 400 VAC and trip class 10. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and terminal spacers are available as accessory.
Unit of Measurement : PCS
Technical
Rated Service Short-Circuit Breaking Capacity (Ics):(230 V AC) 100 kA
(250 V DC) 3 Poles in Series 10 kA
(400 V AC) 100 kA
(440 V AC) 30 kA
(500 V AC) 20 kA
(690 V AC) 3 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):(230 V AC) 100 kA
(400 V AC) 100 kA
(440 V AC) 30 kA
(500 V AC) 20 kA
(690 V AC) 3 kA
Rated Instantaneous Short-Circuit Current Setting (Ii):150 A
Setting Range:6.3 ... 10 A
Rated Operational Power AC-3 (Pe):(400 V) Three Phase 4 kW
Rated Operational Power AC-3e (Pe):(400 V) Three Phase 4 kW
Rated Operational Voltage:Main Circuit 690 V AC
Main Circuit 250 V DC
Rated Operational Current (Ie):10 A
Rated Operational Current AC-3 (Ie):10 A
Rated Operational Current AC-3e (Ie):10 A
Rated Operational Current DC-5 (Ie):10 A
Rated Frequency (f):Main Circuit 50 Hz
Main Circuit 60 Hz
Operating Frequency (fsw):0 ... 400 Hz
Rated Impulse Withstand Voltage (Uimp):Main Circuit 6 kV
Rated Insulation Voltage (Ui):690 V
Power Loss:at Rated Operating Conditions per Pole 0.8 ... 2.0 W
Number of Poles:3
Conventional Free-air Thermal Current (Ith):Main Circuit 10 A
Degree of Protection:Housing IP20
Main Circuit Terminals IP10
Pollution Degree:3
Electrical Durability:50000 cycle
Mechanical Durability:100000 cycle
Terminal Type:Screw Terminals
Connecting Capacity Main Circuit:Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Tightening Torque:Main Circuit 0.8 ... 1.2 N·m
Wire Stripping Length:Main Circuit 9 mm
Recommended Screw Driver:Pozidriv 2
Mounting Position:1 ... 6
Mounting on DIN Rail:TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting Distance:Electrical Conductive Board, Horizontal - Up to 400 V 0 mm
Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm
Electrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 0 mm
Other Device Same Type, Vertical 150 mm
Actuator Type:Rotary Handle
Contact Position Indication:ON / OFF / TRIP
Standards:IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
Remarks:UL508 Self-Protected Combination Motor Controller (Type E) in combination with feeder block S1-M3-xx